Solar 120% Busbar Rule Calculator

Calculate max solar backfeed breaker, allowable inverter AC output, and main breaker derate requirements per NEC §705.12(B).

NEC edition

Inputs

kW

VoltageLab app

Take this toolkit with you on the job

The full VoltageLab electrician app — wire tables, code lookups and job-site calculators offline, on Android and iOS.

⚡ Test your knowledge
Under NEC §705.12(B)(2), what is the maximum backfed solar breaker permitted on a 200A busbar with a 200A main breaker?
  • A. 20 Amps
  • B. 40 Amps
  • C. 60 Amps
  • D. 80 Amps
💡 120% of 200A bus = 240A. 240A − 200A main breaker = 40A maximum allowable backfed solar circuit breaker.
Where must a backfed solar inverter breaker be installed inside a panelboard under the 120% rule?
  • A. Any open slot
  • B. Directly adjacent to main breaker
  • C. At the opposite (bottom) end of the busbar from the utility supply
  • D. In an external subpanel only
💡 NEC §705.12(B)(2) requires the backfed PV breaker to be located at the opposite end of the busbar to prevent bus conductor overloading between sources.

VoltageLab app

Studying for your electrical exam?

Practice NEC exam questions with full explanations and progress tracking, right on your phone.

How it works & the NEC rules behind it

When connecting solar photovoltaic (PV) inverters or battery energy storage systems (ESS) into an electrical panelboard, current can flow from both the utility grid AND the solar inverter simultaneously. To prevent the busbar from overheating, the National Electrical Code (NEC §705.12) restricts total power source input.

The Five Interconnection Methods (NEC §705.12):

  • 1. The 120% Rule — Opposite End (§705.12(B)(3)(2)): Where the solar backfeed breaker is located at the opposite end of the busbar from the main breaker, the sum of the main breaker and 125% of the inverter output must not exceed 120% of the busbar rating:
    (Busbar Rating × 1.20) − Main Breaker = Max Allowable Solar Breaker.
  • 2. Main Breaker Derating: If the required solar backfeed breaker exceeds the 120% limit, you can downsize (derate) the main breaker (e.g., swapping a 200A main breaker for a 175A or 150A main on a 200A busbar) to make room for more solar.
  • 3. The 100% Rule (§705.12(B)(3)(1)): In center-fed panels or panels where opposite-end placement is impossible, the sum of all power source breakers cannot exceed 100% of the busbar rating: Max Solar = Busbar Rating − Main Breaker.
  • 4. Sum of Breakers Rule (§705.12(B)(3)(3)): The sum of all branch-circuit breakers plus the solar breaker cannot exceed the panel busbar rating.
  • 5. Supply-Side Tap (§705.11): Connected between the utility meter and the main service disconnect. Avoids busbar limitations entirely, limited only by service conductor ampacity.

Formulas & equations

Max Solar Breaker (120% Rule) = (Busbar Rating × 1.20) − Main Breaker (§705.12(B)(3)(2)) Inverter Continuous AC Amps = (Inverter kW × 1000) ÷ 240V Min Inverter Breaker Required = Inverter AC Amps × 1.25 (§690.8 / §705.12) Max Inverter AC Power (kW) = [(Max Solar Breaker ÷ 1.25) × 240V] ÷ 1000

NEC reference table

Busbar Rating Main Breaker 120% Bus Capacity Max Solar Breaker Max Inverter Continuous Output
100 A100 A120 A20 A3.84 kW (16.0 A)
125 A100 A150 A50 A9.60 kW (40.0 A)
125 A125 A150 A25 A4.80 kW (20.0 A)
200 A200 A240 A40 A7.68 kW (32.0 A)
200 A (derated)175 A240 A65 A → 60 A11.52 kW (48.0 A)
200 A (derated)150 A240 A90 A17.28 kW (72.0 A)
225 A (Solar Ready)200 A270 A70 A13.44 kW (56.0 A)
400 A400 A480 A80 A15.36 kW (64.0 A)

*Values computed for standard 120/240V single-phase residential services.

Worked example, step by step

Example: Sizing Solar on a Standard 200A / 200A Residential Panel

Given: 200A Busbar, 200A Main Service Breaker, 7.6 kW Inverter @ 240V.

  • Step 1 (Calculate 120% Bus Capacity): 200A × 1.20 = 240 Amps.
  • Step 2 (Determine Max Solar Breaker): 240A − 200A Main = 40 Amps maximum backfeed breaker.
  • Step 3 (Inverter Output Current): 7,600W ÷ 240V = 31.67 Amps continuous AC output.
  • Step 4 (125% Continuous Duty): 31.67A × 1.25 = 39.58 Amps. A standard 40A two-pole breaker is required.
  • Step 5 (Code Compliance): 40A required ≤ 40A max allowed. The system passes compliance! Place breaker at the bottom opposite end.

Frequently asked questions

Under NEC §705.12(B)(3)(2), locating the solar breaker at the opposite end guarantees that current fed from both the grid (top) and the solar array (bottom) flows towards branch breakers in the middle. This physical layout prevents any individual section of the busbar from carrying current in excess of its rated 100% capacity.

A Solar-Ready electrical panel features a 225A rated busbar with a factory-installed 200A main breaker. Under the 120% rule: (225A × 1.20) − 200A = 70A of allowable solar backfeed without requiring main breaker derating or panel upgrades.