Transformer Sizing & OCPD Calculator

Size low-voltage dry-type and liquid transformers (kVA), calculate primary/secondary Full-Load Amps (FLA), size 125% OCPD per NEC §450.3(B), and estimate secondary fault current.

NEC edition

Inputs

V
V
kVA

Enter connected load kVA or desired transformer nameplate kVA

Where the secondary is protected at 125%, Table 450.3(B) permits the primary device to go to 250% — routinely needed to ride through inrush

%

Typical 5–6% for dry-type; used for fault current calculation

VoltageLab app

Take this toolkit with you on the job

The full VoltageLab electrician app — wire tables, code lookups and job-site calculators offline, on Android and iOS.

⚡ Test your knowledge
NEC Article 220 was renumbered in the 2026 code cycle. What is the new article number?
  • A. Art. 100
  • B. Art. 120
  • C. Art. 200
  • D. Art. 230
💡 NEC 2026 renumbered Article 220 (Branch-Circuit, Feeder, and Service Calculations) to Article 120.
Energy Management Systems were moved from Article 750 to which article in NEC 2026?
  • A. Art. 100
  • B. Art. 125
  • C. Art. 130
  • D. Art. 150
💡 NEC 2026 moved Energy Management Systems from Article 750 to Article 130.
Which NEC standard size overcurrent device comes after 90A?
  • A. 95A
  • B. 100A
  • C. 110A
  • D. 105A
💡 Per NEC §240.6(A), the standard sizes are …90, 100, 110, 125… There is no 95A standard size.

VoltageLab app

Studying for your electrical exam?

Practice NEC exam questions with full explanations and progress tracking, right on your phone.

How it works & the NEC rules behind it

Step-down transformers (such as standard 480V Delta to 208Y/120V Three-Phase commercial dry-type units) require careful coordination of primary and secondary overcurrent protection under NEC Article 450 and transformer secondary conductor tap rules under NEC §240.21(C).

Overcurrent Protection Rules (NEC Table 450.3(B)):

  • Primary Only Protection: Where secondary protection is not provided, the primary OCPD must not exceed 125% of primary FLA (or the next standard size up if current is 9A or more).
  • Primary and Secondary Protection: Where secondary OCPD is provided at 125% of secondary FLA, the primary OCPD can be sized up to 250% of primary FLA to prevent nuisance tripping from transformer magnetic inrush current!
  • Secondary Conductor Taps (§240.21(C)): Secondary conductors cannot be protected by the primary OCPD in 3-phase systems. They must terminate in a single OCPD sized to protect the conductors within 10 feet or 25 feet.

Formulas & equations

Single-Phase FLA = (kVA × 1,000) / Voltage Three-Phase FLA = (kVA × 1,000) / (√3 × Voltage) Secondary Fault Current (Isc) = Secondary FLA / (%Z / 100)
Where:
%Z: Transformer percent impedance from nameplate (typically 3.0% to 5.75% for dry-type units).

NEC reference table

Transformer kVA (3-Phase) 480V Primary FLA Primary 125% Breaker 208V Secondary FLA Secondary 125% Breaker
15 kVA18.0 A25 A41.6 A60 A
30 kVA36.1 A50 A83.3 A110 A
45 kVA54.1 A70 A124.9 A175 A
75 kVA90.2 A125 A208.2 A300 A
112.5 kVA135.3 A175 A312.3 A400 A
150 kVA180.4 A250 A416.4 A600 A
225 kVA270.6 A350 A624.6 A800 A
300 kVA360.8 A500 A832.7 A1200 A

Worked example, step by step

Example Calculation: 45 kVA 480V to 208Y/120V 3-Phase Transformer

Scenario: Sizing primary and secondary circuit breakers and secondary available fault current for a 45 kVA dry-type transformer (5.0% impedance).

  • Primary FLA (480V 3Ø): 45,000 / (1.732 × 480) = 54.1 Amps. Primary Breaker (125%) = 54.1 × 1.25 = 67.6A → 70A Breaker.
  • Secondary FLA (208V 3Ø): 45,000 / (1.732 × 208) = 124.9 Amps. Secondary Main Breaker (125%) = 124.9 × 1.25 = 156.1A → 175A Breaker.
  • Available Fault Current (Isc): 124.9A / 0.05 = 2,498 Amps. A standard 10k or 22k AIC secondary distribution panel is fully adequate.

Frequently asked questions

When energized, transformers draw an instantaneous magnetizing inrush current that can reach 10 to 20 times normal full-load current for a few cycles. Sizing the primary breaker with an adequate time-delay trip curve or providing primary protection at 250% (with a 125% secondary OCPD per Table 450.3(B)) prevents nuisance tripping.

No. Under NEC §240.21(C), transformer secondary conductors are taps and do not have overcurrent protection at their point of supply. Therefore, they must comply with the 10-foot or 25-foot transformer secondary tap rules and terminate in a single set of fuses or circuit breaker.