Conduit Body & Mogul LB Calculator

Size standard and Mogul conduit bodies (LB, LL, LR, T, C), cubic inch volume for < #4 AWG, and 6×/8× rules for ≥ #4 AWG per NEC §314.28.

NEC edition

Inputs

wires

VoltageLab app

Take this toolkit with you on the job

The full VoltageLab electrician app — wire tables, code lookups and job-site calculators offline, on Android and iOS.

⚡ Test your knowledge
NEC Article 220 was renumbered in the 2026 code cycle. What is the new article number?
  • A. Art. 100
  • B. Art. 120
  • C. Art. 200
  • D. Art. 230
💡 NEC 2026 renumbered Article 220 (Branch-Circuit, Feeder, and Service Calculations) to Article 120.
Energy Management Systems were moved from Article 750 to which article in NEC 2026?
  • A. Art. 100
  • B. Art. 125
  • C. Art. 130
  • D. Art. 150
💡 NEC 2026 moved Energy Management Systems from Article 750 to Article 130.
Which NEC standard size overcurrent device comes after 90A?
  • A. 95A
  • B. 100A
  • C. 110A
  • D. 105A
💡 Per NEC §240.6(A), the standard sizes are …90, 100, 110, 125… There is no 95A standard size.

VoltageLab app

Studying for your electrical exam?

Practice NEC exam questions with full explanations and progress tracking, right on your phone.

How it works & the NEC rules behind it

Conduit bodies (LB, LL, LR, T, C fittings) provide access to raceways for pulling conductors. Under NEC §314.16(C) and §314.28, sizing rules split sharply based on conductor gauge:

Two Distinct Code Regimes:

  • 1. Conductors Smaller Than #4 AWG (§314.16(C)(1)): Sized by cubic-inch volume. The total volume of all enclosed conductors (based on Table 314.16(B) volume allowances) must not exceed the marked cubic inch capacity on the fitting. Furthermore, the number of conductors cannot exceed the standard Chapter 9 conduit fill limit.
  • 2. Conductors #4 AWG and Larger (§314.28): Must satisfy physical dimension rules to prevent damaging wire insulation during sharp pulls:
    • Angle Pulls (LB, LL, LR fittings, §314.28(A)(2)): The distance from where conduit enters to the opposite wall must be at least 6 times the conduit trade size.
    • Straight Pulls (C fittings, §314.28(A)(1)): Distance between conduit entries must be at least 8 times the conduit trade size.
  • 3. Mogul Conduit Bodies (§314.28(A)(3)): Standard compact LBs are typically NOT listed for 3 or 4 large feeder conductors (e.g. 500 kcmil). When pulling large feeder cables, an elongated Mogul Conduit Body or oversized junction box is legally required.

Formulas & equations

Small Wires (< #4 AWG) Min Volume = Sum(Conductor Count × Table 314.16(B) in³) Angle Pull (LB/LL/LR) Min Dimension = 6 × Conduit Trade Size (§314.28(A)(2)) Straight Pull (C Body) Min Dimension = 8 × Conduit Trade Size (§314.28(A)(1))

NEC reference table

Conduit Trade Size Standard LB Internal Length Required Angle Pull (6× Rule) Required Straight Pull (8× Rule) Mogul LB Required for ≥ #4 AWG?
1/2" (16 mm)~4.0 inches3.0 inches4.0 inchesNo (small conductors)
3/4" (21 mm)~4.7 inches4.5 inches6.0 inchesNo (small conductors)
1" (27 mm)~5.5 inches6.0 inches8.0 inchesMogul required if #4+
1-1/4" (35 mm)~6.5 inches7.5 inches10.0 inchesMogul required if #4+
2" (53 mm)~9.5 inches12.0 inches16.0 inchesMogul LB Mandatory
3" (78 mm)~13.0 inches18.0 inches24.0 inchesMogul LB Mandatory
4" (103 mm)~17.0 inches24.0 inches32.0 inchesMogul LB Mandatory

Worked example, step by step

Example: Sizing an LB for 3 × 3/0 AWG Copper in 2" EMT Conduit

Given: 2" EMT Conduit with 3 × 3/0 AWG Copper conductors.

  • 1. Check Conductor Size: 3/0 AWG is ≥ #4 AWG → NEC §314.28 applies.
  • 2. 6× Angle Pull Rule: 6 × 2.0 inches = 12.0 inches minimum distance to opposite wall.
  • 3. Standard LB Evaluation: A standard 2" aluminum LB has an inside length of ~9.5", which is LESS than 12.0" (Code Violation!).
  • 4. Solution: Install a 2" Mogul LB (e.g. Appleton / Crouse-Hinds Mogul LB) with listed 13.5"+ cover opening, or install a 12"×12" pull box.

Frequently asked questions

Under NEC §314.16(C)(2), splices or taps are ONLY permitted in conduit bodies that are durable and legibly marked by the manufacturer with their cubic inch volume, and where the volume satisfies the standard box fill requirements of §314.16(B).

A 200A residential service uses 2" conduit with #2/0 Cu or 4/0 Al conductors (which are ≥ #4 AWG). Under §314.28(A)(2), a 6× distance (12 inches) is required. Standard short 2" LBs crush 4/0 conductors against the back wall during the turn. A Mogul LB or pull box is required.