How it works & the NEC rules behind it
Bonding jumpers provide the low-impedance electrical path necessary to conduct fault currents back to the source and trip overcurrent protective devices. Under NEC §250.102, bonding jumpers installed on the supply side of service overcurrent devices are sized using Table 250.102(C)(1) based on the size of the largest ungrounded phase conductor.
Types of Bonding Jumpers (NEC Article 250):
- 1. Main Bonding Jumper (MBJ, §250.28): Connects the grounded circuit conductor (neutral) to the equipment grounding conductor / enclosure at each service disconnect.
- 2. System Bonding Jumper (SBJ, §250.30(A)(1)): Connects the grounded conductor of a separately derived system (transformer or generator) to the equipment ground.
- 3. Supply-Side Bonding Jumper (SSBJ, §250.102(C)): Installed on the supply side of service disconnects (such as between CT cabinets, meter sockets, and service panels).
- 4. The 12.5% Area Rule (§250.102(C)(1) Note 1): Where the largest ungrounded phase conductor (or sum of parallel conductors) exceeds 1,100 kcmil Copper or 1,750 kcmil Aluminum, the bonding jumper must have an area not less than 12.5% of the total phase conductor cross-sectional area.