Transformer Sizing Calculator — NEC 450 + IEC | VoltageLab
⚡ Electrical Calculator

Transformer Sizing Calculator

NEC 450 · IEC 60076 · KVA Sizing · Full Load Amps · OCPD Guidance

⚙️ System Configuration
📋 Load Input
📐 Sizing Options

Primary voltage is optional — used to calculate primary full-load amps and NEC 450.3 OCPD sizing.

Please fill in all required fields.
Calculated Load
(kVA)
With Margin
(kVA)
📊 Load Breakdown
Calculated load
Safety margin (+25%)
Minimum required
Next standard transformer size ↓
Headroom above minimum
Standard Sizes — Nearest Options
💡
Need NEC and IEC code lookup on the job?
VoltageLab's AI Code Lookup covers NEC Article 450, IEC 60076, BS7671, AS/NZS 3000, and CEC — explained in plain English and searchable from your phone in seconds. Built for electricians, engineers, and exam candidates worldwide.

Single-phase: kVA = (V × I) / 1,000  |  Three-phase: kVA = (√3 × V × I) / 1,000
From kW: kVA = kW / PF  |  FLA = (kVA × 1,000) / V (1Φ)  or  (kVA × 1,000) / (√3 × V) (3Φ)
NEC 450.3(B): Primary OCPD ≤ 125% × primary FLA (for FLA ≥ 9 A). Standard sizes per NEC 240.6(A).
For non-linear loads (VFDs, UPS, computers), apply additional K-factor derating — consult transformer manufacturer.
Results are indicative. Always verify with a licensed electrical engineer before specifying equipment.