Motor Branch Circuit Calculator

NEC Article 430 · Conductors (430.22) · Protection (430.52) · Overloads (430.32) · EGC (250.122) · Tables 430.248 & 430.250

⚙️ Motor Specifications

Most general-purpose motors have SF ≥ 1.15. Check nameplate.

🔒 Protection Device Selection

Inverse-time breakers and dual-element fuses are most common for motor circuits.

Please fill in all required fields.
NEC Table Full-Load Current (FLC)
— A
Table 430.250
🔌
Branch
Conductor
NEC 430.22
🔒
OCPD
Max Size
NEC 430.52
🌡️
Overload
Relay Max
NEC 430.32
🌍
EGC Min
Size
NEC 250.122
📊 Step-by-Step Calculation — NEC Article 430
🔒 Protection Device Comparison — NEC Table 430.52
Device Type % Calc (A) Std Size
💡
Need to look up NEC Article 430 on the job?
VoltageLab's AI Code Lookup has every NEC Article 430 section referenced and explained — motor circuits, conductor sizing, protection coordination, and overload requirements. Used by thousands of electricians in the field and studying for their journeyman and master exams.

Branch conductor: NEC 430.22 — ampacity ≥ 125% × FLC  |  Protection: NEC 430.52 — max rating per Table 430.52 % × FLC, next standard size up  |  Overload: NEC 430.32 — 125% (SF ≥ 1.15) or 115% (others)  |  EGC: NEC Table 250.122 based on OCPD rating
FLC from NEC Table 430.248 (single-phase) or Table 430.250 (three-phase) per NEC 430.6(A)(1) — nameplate current not used for circuit sizing.
Standard device sizes per NEC 240.6(A). Results are indicative. Verify with a licensed electrical engineer before installation.